Items |
275KXX-120VAC 275 Series - Motor Reversing Contactors |
275KXX-240VAC 275 Series - Motor Reversing Contactors |
275KXX-24VAC 275 Series - Motor Reversing Contactors |
275KXX-24VDC 275 Series - Motor Reversing Contactors |
275KXX-115VDC 275 Series - Motor Reversing Contactors |
|||||
Series | N/A 275 | |||||||||
Contact Arrangement | N/A KXX (2X 3PST – N.O. – double make) | |||||||||
Optional Features | N/A | |||||||||
Coil Voltage | N/A 120 VAC | N/A 240 VAC | N/A 24 VAC | N/A 24 VDC | N/A 115 VDC | |||||
Contact Configuration | N/A 3PST-NO Double Make per side | |||||||||
Contact Material | N/A Silver Alloy | |||||||||
Contact Rating | N/A 15 A | |||||||||
Contact Rating 120 / 240VAC Resistive | N/A 15/10 A | |||||||||
Motor 120VAC 1 Phase | N/A 1 hp | |||||||||
Motor 240VAC 1 Phase | N/A 1.5 hp | |||||||||
Motor 240VAC 2-3 Phase | N/A 3 hp | |||||||||
Motor 480 / 600VAC 2-3 Phase | N/A 3 hp | |||||||||
Contact Resistance, Initial | N/A 100 milliohms max at 6VDC | |||||||||
Coils Available | N/A AC and DC | |||||||||
Nominal Coil Power AC | N/A 17 VA | |||||||||
Nominal Coil Power DC | N/A 4.9 W | |||||||||
Input Voltage Tolerance - AC | N/A 85% to 110% of nominal | |||||||||
Input Voltage Tolerance - DC | N/A 80% to 110% of nominal | |||||||||
Drop-out voltge | N/A 10% of nominal | |||||||||
Duty | N/A Continuous | |||||||||
Operate Time (max) | N/A 50 ms | |||||||||
Release Time (max) | N/A 30 ms | |||||||||
Across Open Contacts | N/A 2500 Vrms | |||||||||
Between Mutually Insulated Point | N/A 2500 Vrms | |||||||||
Insulation Resistance | N/A 1000 megohms at 500Vrms | |||||||||
Operating | N/A -34 to 74 ºC-30 to 165 ºF | |||||||||
Storage | N/A -40 TO 105 ºC-40 to 221 ºF | |||||||||
Electrical (full load) | N/A 100,000 | |||||||||
Mechanical (no load) | N/A 5,000,000 | |||||||||
Mounting Position | N/A Vertical , Contacts Up | |||||||||
Enclosure | N/A Semi-Enclosed | |||||||||
Weight | N/A 16.0 oz406 g | |||||||||
|