Under / Over voltage sensing relay incorporating 219 series internal components coupled with an electronic module. Pull-in voltage is adjustable from 85 to 135VAC for frequencies ranging from 50 to 400 hertz. Hysteresis is typically set for a 4 volt differential but can be user adjustable from 3 to 14 volts when external connections are available.
Additional contact configurations and coil options are available – please use the RFQ/RFI tab above to submit your request.
Additional contact configurations and coil options are available – please use the RFQ/RFI tab above to submit your request.
Unit of Measure
Specifications
|
Contacts
|
Coil
|
Dielectric Strength
|
Temperature
|
Life Expectancy
|
Miscellaneous
Specifications
Series |
N/A 349 |
Contact Arrangement |
N/A BBX (2 Pole NO & DPDT) |
Standard Features |
N/A Plug-in with polycarbonate cover |
Optional Features |
N/A Bifurcated contacts (5 Amps max) |
Coil Voltage |
N/A 85-135 VAC |
Contacts
Contact Configuration |
N/A Up to 4 pole |
Contact Material |
N/A Silver Alloy Gold Diffused |
Contact Rating |
N/A 10 A |
Contact Rating 120 / 240VAC Resistive |
N/A 10 A / 10 A |
Contact Rating 28VDC Resistive |
N/A 10 A |
Minimum Contact Load |
N/A 500 mW |
Contact Resistance, Initial |
N/A 100 milliohms max at 6VDC |
Coil
Coils Available |
N/A AC |
Power Consumption |
N/A 5 VA |
Input Voltage Absolute Maximum |
N/A +60% of nominal |
Pickup Voltage Range |
N/A 3 to 14 volts over drop out |
Dropout Voltage Range |
N/A 85 to 135VAC |
Transient Protection |
N/A Yes |
Duty |
N/A Continuous |